Specification: Device Name: Battery Charger Type: TE-BC-3P5-110V-60A-THY (Standing built-up panel) Input: 380 Vac, 3 Phase, ± 10% Voltage Output: 110 Vdc (Adjustable ± 25%), Constant Voltage Current Output: 60 Ampere (max) Ripple Voltage: <1% Ambient Temperature: 0-40°C, Humidity 90% Noise Level: Max 65 dB Special Features: Manual mode, Auto Boost Additional with Timer Float Equipped with: Surge protector up to 1.5 kV, 40kA Over Voltage Protector: up to 500 VAC Display: Analog for Load, Battery Charge Current, Voltage. Basic Principles of Battery Charger Battery charger is used to charge the battery so that the battery voltage is always maintained and ready as a backup to supply the DC system if there is a disturbance to the AC input. The power regulator output uses a thyristor (SCR), for 3-phase or 1-phase input. Complete Specification 1. Input dan Output : According to order (customize). 2. Automatic Charger Control. Simplify the operating system and do not need special care. 3. Installed protection :
4. Automatic Transfer System Equipped with a diode blocker for easy transfer to the DC system (for 2 redundant battery chargers). Its function is when there is interference with one rectifier, it will not affect the other rectifier. 5. Boost Timer For boost charger timer. Can be set 0 - 30 hours. It's on the mimic panel, so it's easy to reach. 6. Announciator To display an indication of what happened to the battery charger. Charger ON
7. Panels The size of the panel is adjusted to the avaliable space, taking into account the ease of access for maintenance. Related project
|